Traditional versus Custom Hazardous Area Classification

Wood Dust

Traditional versus Custom Hazardous Area Classification


Brian Schneider

Canary HLE President,
Hazardous Locations industry expert

Brian Schneider is a Hazardous Locations industry expert with over 25-years experience working with clients including Lockheed-Martin and Siemens. He also instructs CompEx Ex12 (Application Design Engineering); CompEx Ex01-Ex04 (gases and vapours), CompEx Foundations, CompEx NEC 500 and CompEx NEC 505 Foundation courses. He specializes in intrinsic safety and flame-proof/explosion designs and evaluations. Brian is a 18-year member of the Canadian Electrical Code (CEC) Section 18 Committee and has designed and built testing labs in Canada and Europe.

Safety is the primary directive when undertaking the evaluation of a hazardous area. In that regard, the methodology applied to conduct a Hazardous Area Classification (HAC) requires careful review and application of Codes, Standards and Regulations . They provide the guidance to determine the physical extents of the hazardous area. Further, it is a requirement that a HAC be undertaken in businesses where operations or processes create a potentially explosive area .

Figures 1a and 1b illustrate the difference that undertaking a custom HAC can make in defining the HAC. In Figure 1a, the traditional method classifies the hopper containing explosive dust as Zone 20 (within the hopper) and Zone 21 for a prescribed area outside of the hopper. The area classified as Zone 22 comprises a large area surrounding the Zone 20 and Zone 21 areas.

Canary_Blog_Traditional_0007_Traditional
Figure 1a: HAC result with traditional methodology
Canary_Blog_Traditional_0007_Traditional
Figure 1b: Custom HAC result using CFD modelling

Figure 1b illustrates the resultant area classification using Computational Fluid Dynamics (CFD) modelling. After airflow, intake and exhaust volumes and velocities are measured, the data is uploaded to a 3-D modelling program. The ensuant product is then modeled in the CFD program. The result is a much more precise and accurate hazardous area classification.  In some cases, the HAC may be calculated to be much smaller than that reached using traditional methods. This may result in massive costs savings while keeping the same measure of safety as when the traditional method is applied. One other advantage of using CFD modeling is that when modifications have been made to equipment or the area, it is easier and faster to assign the new HAC.

Note: There are occasions when the classified area may be larger. The risk of an adverse event is increased if traditional HAC methodology is applied.

Detailed Methodology of Custom Hazardous Area Classification

In the simplified example described herein, there is a building with a single hopper containing an explosive dust. There is an air inlet in the ceiling and an exhaust on the floor.

Figure 2 is a 3D drawing of the air geometry surrounding the hopper located within a building (front view):

Canary_Blog_Traditional_0007_Traditional
Figure 2: Volume of air in building (Autodesk Fusion licensed software)

The hopper section handles an explosive dust. Air enters the building through the air Inlet and exhausts on the lower right side of the building.

Canary_Blog_Traditional_0007_Traditional
Figure 3: Backside of the building showing air inlet and exhaust outlet

A Hazardous Area Classification (Figure 4) using traditional methodology may have produced the following:

Canary_Blog_Traditional_0007_Traditional
Figure 4: Hazardous Area Classification depiction using traditional methodology

The 3-D model produced in the Fusion program was uploaded to the Computational Fluid Dynamics program (SimScale GmbH); it produced the visualization of air movement as seen in Figure 5.

Canary_Blog_Traditional_0007_Traditional
Figure 5: CFD modelling of air movement inside building. Note: the size of the directional arrows (circled in red) is proportional to the air velocity leaving the building.

The different colors within the building represent the magnitudes of the velocities within the geometry of air.

For this example, the only source of release (SOR) was identified and is represented by the blue sphere in Figure 6.

Canary_Blog_Traditional_0007_Traditional
Figure 6: Source of Release (SOR) of the explosive dust is represented by the blue circle.
Canary_Blog_Traditional_0007_Traditional
Figure 7: Dust leak envelope and its path; red area represents the SOR

Figure 7 is the visualization of the CFD output of airflow movement and dust leak path.

The Red/Orange/Yellow/Green area represents the dust leak envelope, with the highest concentration represented by the red area. The white box within Figure 7 is the sample point of the concentration at the red pin point.

Figure 8 depicts the HAC with CFD modelling applied.  There is a considerable decrease in the area being classified.

Canary_Blog_Traditional_0007_Traditional
Figure 8: Resultant HAC using CFD modelling

The IEC 60079-1, IEC 60079-2 and the Energy Institute Part 15 Standards concur that Computational Fluid Dynamic modelling is an acceptable methodology to apply when undertaking a hazardous area classification.


CANADA
Canadian Electrical Code Part 1 CEC C22.1-24

18-004 Classification of hazardous locations (see Appendices B, J and L)

  1. Hazardous locations shall be classified according to the nature of the hazard, as follows:
    1. explosive gas atmospheres; or
    2. explosive dust atmospheres.
  2. Hazardous location classification shall be carried out and documented by qualified persons.
  3. Hazardous location classification required by Subrule 2) shall be authenticated by the person assuming responsibility for the classification.

 

USA
Occupational Safety and Health Act of 1970

36 FR 17850, Sept. 4, 1971, PART 1903—INSPECTIONS, CITATIONS AND PROPOSED PENALTIES

1910.307(b)

Documentation. All areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007, shall be properly documented. This documentation shall be available to those authorized to design, install, inspect, maintain, or operate electric equipment at the location.


EUROPE
DIRECTIVE 1999/92/EC OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 December 1999 on minimum requirements for improving the safety and health protection of workers potentially at risk from explosive atmospheres (15th individual Directive within the meaning of Article 16(1) of Directive 89/391/EEC).

Article 7:

  1. The employer shall classify places where explosive atmospheres may occur into zones in accordance with Annex I (Source for Annexes I, II and III: https://www.legislation.gov.uk/eudr/1999/92/annexes; accessed 24Oct2025).
  2. The employer shall ensure that the minimum requirements laid down in Annex II are applied to places covered by paragraph 1.
  3. Where necessary, places where explosive atmospheres may occur in such quantities as to endanger the health and safety of workers shall be marked with signs at their points of entry in accordance with Annex III.